The disturbance occurred around 8:16 am when power generation dropped to 00MW, with many states reporting blackouts.

Checks confirmed that power generation stood at 3,042 megawatts at 8 am and peaked at 3,968MW at 7 am.

However, generation dropped to 47MW as of 9 am, with allocation to power distribution companies standing at 0.00MW at the time of filing this report.

However, data gleaned from the Nigerian System Operator’s portal (niggrid.org), revealed that the grid recorded an unprecedented zero Megawatts (MW) as of 8:16 am today.

The data also revealed that all 22 generation companies (GenCos) are down as of the time of this report.

Reacting to the incident, TCN’s General Manager, Public Affairs, Ndidi Mbah, explained that the bus section of a current transformer exploded at 330kV Jebba Transmission Substation, triggering the temporary shutdown.

“The Transmission Company of Nigeria hereby states that the national grid experienced a temporary disturbance at about 8:15 am, today, 19th Oct. 2024.

“According to the report from the NCC, the bus section of a current transformer exploded at 330kV Jebba Transmission Substation and as expected, the protection system was activated, and this promptly opened the busbars to curtail the explosion, thereby preventing the outbreak of fire and further damage to adjacent equipment.

“The action of the protection system led to a temporary disturbance on the grid.

“Our engineers at Jebba have successfully carried out switchings, isolating the faulty current transformer. They have equally reconfigured the busbar arrangement, restoring power supply to the station, and other parts of the grid,” Mbah said in a statement.